Description

The detector has wide-angle sensitivity that can reliably and quickly detect weak ultraviolet radiations emitted by flame. It will not react to room illuminations, infrared or other light sources unrelated to real fire.

 

Installation Instructions

Install at obstruction-free places.

Avoid installing near mercury lamps, halogen lamps and sterilization lamps.

Avoid installing within sensitive range of welding sparks and radiation.

 

Applications

Premises with higher ceilings: theater, gym, storage, gallery or warehouse, etc.

Places where fires happen easily: places storing with combustible goods, gas stations, factory working places, machine rooms, etc.

Ventilate places: open markets, station platforms, hotel lobbies, department stores, etc. (places that smoke and heat can not gather during early period of fire)

Others: tunnels, computer rooms, etc.

 

Specifications

Model

AH-0014

Type

2-wire

3-wire

4-wire

Alarm Contact

N/A

N/A

0.8A @30V DC 0.4A @125V AC

Voltage Range

12 ~ 30V DC

Alarm Current
@24V DC 470Ω

40mA

40mA

35mA

Standby Current
@24V DC 470Ω

Under 100μA

Sensor Type

Ultraviolet

Sensitivity Angle

120o

Sensitivity Range

It can detect flame of 15mm at distance of 3m

Ambient Temperature

-10oC ~ +55oC

Material

Fire-proof plastic

Dimensions (mm)
Dia. x H

111 x 47

Weight

Aboaut 170g

Color

White

 